Description
-
Manufacturer : ICS Triplex
-
Product No. : 9802*3/9832*1
-
System Supply Voltage Range : 20 to 32V dc
-
Number of Inputs : 40 Channels
-
User Defined Thresholds : 4-off
-
Input Current Range : 0-22mA
-
Input Voltage Range : 0-6 Vdc
-
Sample Update Time : 0.5ms
-
Resolution : 3.9uA (1/256mA)
-
Safety Accuracy : +/- 1% of full scale
(default threshold above which 0x70nn series slice discrepancy faults are raised)
-
Calibration Accuracy : 0.03%
-
Recommended input channel calibration check
-
interval : 2 years
-
Circuit Type : Fault tolerant, fully triplicated with optional line monitoring
-
Fusing : None, external if required
Intrinsic Safety External barrier
Sequence of Events
-
Event Resolution : 1ms
-
Time-stamp Accuracy : ±0.5 ms
-
Field Common Isolation
-
Sustained Working : ±250V dc
-
Maximum Withstanding : ±2.5kV dc
-
Channel to Channel Crosstalk : -40 to –60 dB
-
Power Consumption : 15 – 18W
-
Self-Test Interval : 2 minutes
-
Operating Temperature : -5°C to 60°C (23°F to 140°F)
-
Non-operating Temperature : -25°C to 70°C (-13°F to 158°F)
-
Temperature change : 0.5ºC/min
-
Operating Humidity : 10 – 95% RH non-condensing
-
Environmental Specifications : Refer to Document 552517
-
Dimensions
Height : 266mm (10.5ins)
Width : 31mm (1.2ins)
Depth : 303mm (12ins)
-
Weight : 1.149kg (2.5lbs)
-
Real Time Clock Resolution : 100µSec
-
Shipping Weight : 2 Kg